SPAZIO
- IP40
- IK04
- LED 4000ºK
- Duration 1-3 h
- Lumen output range: 145-200 lm.
- Batteries: Ni-Mh. Ecological and recyclable
- Applications: Indoor. Decorative. Architectural.
- Work type: Maintained / Non Maintained
- System available: Standard, Self-Test, Addressable Wireless
- Two lens options:
- Escape Route Lighting (LED D)
- Open Area / Anti-panic Lighting (LED R)
- Slave luminaire for Centralized System Battery
File download:
Available with:LiFePO4 Technology
- Measurements
- Round Spazio Emergency lighting
- Square Spazio Emergency lighting
- Lighting spacing LSQ-3181 and LSR-3181
- Lighting spacing LSQ-3180 and LSR-3180
- Installation manuals
Spazio LSR | Spazio LSQ | Electronics and battery |
![]() |
![]() |
![]() |
Minimum height of false ceiling: 80 mm.
Lm. | Type* | Lamp (W) | Dur. (h) | Battery Units / A/h | Units Box | Standard Ref. | Photometric Ref. | Self-Test Ref. | Self-Test Curve | Ref. Wireless | Addressable Wireless Curve |
200 | M/NM | Led R | 1 | 4 x 1.1 | 12 | LSR3180ECP | LDT | LSR3180EXP | LDT | LSR3180EDPW | LDT |
200 | M/NM | Led D | 1 | 4 x 1.1 | 12 | LSR3181ECP | LDT | LSR3181EXP | LDT | LSR3181EDPW | LDT |
145 | M/NM | Led R | 3 | 4 x 1.6 | 12 | LSR3140ECP3 | LDT | LSR3140EXP3 | LDT | LSR3140EDP3W | LDT |
145 | M/NM | Led D | 3 | 4 x 1.6 | 12 | LSR3141ECP3 | LDT | LSR3141EXP3 | LDT | LSR3141EDP3W | LDT |
*M: Maintained. The luminaire operates from the normal or emergency supply at all material time.
*NM: Non Maintained. The luminaire operates from emergency supply only upon failure of the normal mains supply.
*M/NM: Same working as Maintained luminaire, with a third terminal which allows to switch off the luminaire when connected to mains supply.
More information about our systems: AutoTest y Wireless
Lm. | Type* | Lamp (W) | Dur. (h) | Battery Units / A/h | Units Box | Standard Ref. | Photometric Ref. | Self-Test Ref. | Self-Test Curve | Ref. Wireless | Addressable Wireless Curve |
200 | M/NM | Led R | 1 | 4 x 1.1 | 12 | LSQ3180ECP | LDT | LSQ3180EXP | LDT | LSQ3180EDPW | LDT |
200 | M/NM | Led D | 1 | 4 x 1.1 | 12 | LSQ3181ECP | LDT | LSQ3181EXP | LDT | LSQ3181EDPW | LDT |
145 | M/NM | Led R | 3 | 4 x 1.6 | 12 | LSQ3140ECP3 | LDT | LSQ3140EXP3 | LDT | LSQ3140EDP3W | LDT |
145 | M/NM | Led D | 3 | 4 x 1.6 | 12 | LSQ3141ECP3 | LDT | LSQ3141EXP3 | LDT | LSQ3141EDP3W | LDT |
*M: Maintained. The luminaire operates from the normal or emergency supply at all material time.
*NM: Non Maintained. The luminaire operates from emergency supply only upon failure of the normal mains supply.
*M/NM: Same working as Maintained luminaire, with a third terminal which allows to switch off the luminaire when connected to mains supply.
More information about our systems: AutoTest y Wireless
Spacing for 1 lux at different mounting heights. Escape Route Lens D
Height | ![]() |
![]() |
Position![]() |
![]() |
![]() |
2,0 | 7,79 | 19,86 | 12,63 | 6,39 | 2,39 |
2,5 | 8,10 | 21,04 | 13,50 | 6,68 | 2,43 |
3,0 | 8,24 | 21,94 | 13,96 | 6,81 | 2,42 |
3,5 | 8,23 | 22,44 | 14,20 | 6,89 | 2,39 |
4,0 | 8,04 | 22,71 | 14,30 | 6,85 | 2,28 |
Spacing for 1 lux at different mounting heights. Open Area / Anti-panic Lens R
Altura | ![]() |
![]() |
Posición![]() |
![]() |
![]() |
2,0 | 3,55 | 8,64 | 8,64 | 8,64 | 3,55 |
2,5 | 3,80 | 9,54 | 9,54 | 9,54 | 3,80 |
3,0 | 3,96 | 10,26 | 10,26 | 10,26 | 3,96 |
3,5 | 4,05 | 10,72 | 10,72 | 10,72 | 4,05 |
4,0 | 4,04 | 11,07 | 11,07 | 11,07 | 4,04 |
Download installation manual, electrical connection / test and instructions for use: